Cabling and protections

Radiaris pre-sizes the cable cross-sections and the protections, and calculates the real ohmic losses of each circuit instead of applying a fixed 1 %. It is enabled in 6 · Advanced settings → Cabling and protections; if you enable it, it replaces the «DC cabling» of the aggregated losses.

Pre-sizing

The results are a design guide based on the Spanish Low Voltage Regulation (REBT). The final project or technical report must check the real conditions of the installation.

What it calculates

DC side (one cable per string, from the modules to the inverter) - Minimum cross-section that meets the ampacity and the voltage drop. - Hour-by-hour Joule loss: P = I²·R, with I = P_string / V_mpp and R = 2·ρ(T)·L / S. - String fuses when there are 3 or more strings in parallel (criterion of IEC 62548).

AC side (line from the inverter to the distribution board) - Minimum cross-section, design current and circuit breaker. - Loss: single-phase P = I²·2ρL/S (I = P/V); three-phase P = 3·I²·ρL/S (I = P/(√3·V)). - 30 mA type A residual current device on a separate circuit for homes or residential areas. - Protective conductor according to the ITC-BT-19 table.

Regulations applied (REBT, RD 842/2002)

Aspect Reference
Ampacity (copper, in air, 40 °C; PVC or XLPE/EPR; 2 or 3 conductors) ITC-BT-19, Table 1 (UNE 20460-5-523)
Ambient temperature other than 40 °C ITC-BT-07, Table 13
Cable grouping ITC-BT-06, Table 6
Array connection cables: ampacity ≥ 125 % of the array maximum; drop ≤ 1.5 % ITC-BT-40, section 5
Overload protection: Ib ≤ In ≤ Iz ITC-BT-22 (UNE 20460-4-43)
30 mA type A residual current device ITC-BT-40, section 4.3
Protective conductor cross-section ITC-BT-19, Table 2
Maximum DC voltage 1,500 V (art. 4 of the Regulation)

Editable parameters

Parameter Default
Length of each string to the inverter (one way) 15 m (you can set one length per plane)
Inverter → distribution board length 10 m
Maximum DC drop 1 % of Vmp
Maximum AC drop 1,5 %
DC and AC cross-section Automatic (the smallest standard size that complies) or fixed
Average conductor temperature (losses) 50 °C
AC voltage 230 V single-phase / 400 V three-phase, depending on the inverter
DC: installation method, insulation, ambient temperature C, XLPE, 60 °C (cables under the modules and in the sun)
AC: installation method, insulation, ambient temperature B, XLPE, 40 °C
Grouped circuits DC: the parallel strings of the MPPT; AC: 1

Where to see the result

In 7 · Scenarios and report → Analysis details: table of cross-sections and protections, voltage drop of each circuit and total annual cabling loss. The loss is included in the loss waterfall.

Ohmic losses (calculation)

The resistivity of copper is calculated at the conductor temperature:

ρ(T) = ρ20 · (1 + α · (T − 20))

The DC loss is capped at 10 % of the power as a safeguard against absurd data.

Is something missing or wrong? Write to us at hola@radiaris.com. Last reviewed: 26 October 2026.